Skip to content
SimpleConvertSimpleConvert

Wire Gauge Chart

Full AWG reference table: diameter in millimetres and inches, cross-section in mm², copper resistance per kilometre, and the SWG equivalent.

Formula
d(mm) = 0.127 × 92^((36 − n) ÷ 39) · A(mm²) = π ÷ 4 × d²

How to use it

  • Scroll the table or type a gauge number to filter it.
  • Compare the mm² column when matching an American cable to a metric one.
  • Use the Ω/km column with the voltage-drop calculator to size a long run.

American Wire Gauge (AWG) sizes conductors on a logarithmic scale: gauge 36 is fixed at 0.005 in diameter, gauge 0000 (4/0) at 0.46 in, and every step in between follows a constant ratio of 39 steps between those two points. That single geometric rule is what generates every diameter, cross-section and resistance figure in the table below — nothing is looked up from a separate list.

This page gives the full AWG reference at once: diameter in millimetres and inches, cross-sectional area in mm², copper resistance per kilometre, and the closest SWG (British Standard Wire Gauge) equivalent for comparing against non-American cable.

The formula

d(mm) = 0.127 × 92^((36 − n) ÷ 39), where n is the AWG number. Cross-sectional area follows directly from the diameter: A(mm²) = π ÷ 4 × d². A smaller gauge number means a thicker wire — the numbering runs backward from what feels intuitive, because it originally counted how many times a wire had been drawn through progressively narrower dies.

Why the numbers count down as wire gets thicker

AWG traces back to a physical manufacturing process, not an abstract size chart. A wire started as a thick rod and was drawn through a die to thin it, then drawn again through a narrower die, and so on. The gauge number was simply how many passes it had been through — more passes meant a thinner wire and a higher number. Modern wire is not actually made this way anymore, but the numbering stuck.

Reading 1/0 through 4/0

Gauges thicker than 1 AWG are not written as negative numbers on cable — they use the 'aught' notation instead: 1/0 (one-aught), 2/0, 3/0 and 4/0. In the formula above they correspond to n = 0, −1, −2 and −3 respectively. 4/0 is a genuinely substantial conductor, used for heavy service entrance cable and welding leads rather than anything found in a typical household circuit.

Matching AWG to metric cable

American and metric wire are sized on entirely different systems — AWG by a logarithmic gauge number, metric cable directly by cross-sectional area in mm². The mm² column is the bridge between them: a 12 AWG conductor, at roughly 3.31 mm², is close enough to a metric 3.3 mm² or a 4 mm² cable to substitute in most low-voltage work, though always check the actual current rating for the specific insulation and installation method rather than the cross-section alone.

Using this with a voltage-drop calculation

The Ω/km column is the figure a voltage-drop calculation actually needs, since resistance — not gauge number — is what determines the drop across a run of a given length and current. Read the resistance for a candidate gauge, run it through the voltage-drop calculator for the run length and load current, and if the result exceeds about 3% on a branch circuit, move up to the next thicker gauge and check again.

Questions people ask

Why do AWG numbers get smaller as the wire gets thicker?

The gauge number originally counted how many times the wire was drawn through a die. More passes meant a thinner wire and a higher number, and the naming stuck.

What do 1/0, 2/0 and 4/0 mean?

They are the gauges above 1, written as 0, 00, 000 and 0000 and spoken as one-aught through four-aught. In the formula they are n = 0, −1, −2 and −3.

Where does the AWG formula come from?

American Wire Gauge is defined geometrically: gauge 36 is 0.005 in and gauge 0000 is 0.46 in, with 39 equal ratio steps between them. That gives d(mm) = 0.127 × 92^((36 − n) ÷ 39).

How much voltage drop is acceptable?

The usual guideline is 3 % on a branch circuit and 5 % from the supply to the furthest load. Above that, lights dim visibly and motors run hot, so step up to a thicker conductor.

Does temperature change the answer?

Yes. Copper resistance rises about 0.4 % per °C, so a hot cable in a conduit drops more voltage than the 20 °C figures used here. Allow some margin for a hot installation.

Runs entirely in your browser. Nothing you type is uploaded, logged or shared.

Last updated 17 August 2026